Doble F6150e- Dispozitiv de testare relee de protecție
Doble F6150e este un dispozitiv versatil pentru testarea releelor de protectie.
Acest tester de relee efectuează de la cele mai simple până la cele mai complexe teste. F6150e este disponibil în diferite configurații.
Fie că aveți nevoie pentru a testa o componentă specifică sau pentru a testa o întreagă schemă, F6150e este soluția dovedită pentru a evalua performanța sistemului de protecție.
Caracteristici:
Beneficii:
DOBLE F6150e/sv TECHNICAL SPECIFICATIONS
The F6150e/sv line of Power System Simulators is designed for simulation tests on relay and protection schemes.
CURRENT GENERATOR (12 TOTAL) GRAPHICAL VIEW
Description Covertible V/I Sources Current sources Convertible V/I Sources Output Current
For High power at low
current applications,
Electromechanical
relay testing, busbar
protection, Main 1 & All Current
Application
Main 2 dynamic and protections
transient tests.
Used with the Current
sources for more than
6 source applications.
Current Settings
6-phase AC 6X 0...1.5 A 6X 0....35 A
(L-N) Current Sources Output Current
3-phase AC 3X0….3 A 3X 0….70 A
(L-N)
1-phase AC 1X 0….9 A 1x 0….210 A
(LL-LN)
DC
1 X 0…. 6.36 A 1X 0….140 A
(LL-LN)
8.75 A, 17.5 A, 35 A,
Available Range 0.5 A, 1 A, 1.5 A, 3 A, 9 A
70 A, 105 A, 210 A
Power
6x1.5A @ 97.5 VA 6X35A @ 131.25 VA
6-phase AC Short Duration** Long Duration*
(L-N) 6X17.5A @ 87.5 VA
6X1A @ 75 VA Continuous Continuous Voltage Generator Output Voltage
3X3A @ 195 VA 3X70A @ 262.5 VA
3-phase AC Short Duration** Long Duration*
(L-N) 3X2A @ 150 VA 3x35 A @ 175 VA
Continuous Continuous
1X9A @ 585 VA 1x210 A @ 787.5 VA
1-phase AC Short Duration** Long Duration*
(LL-LN) 1X6A @ 450 VA 1x105 A @ 625 VA
Continuous Continuous
1X6.36A @ 585 W 1X140A @ 787.5 W
DC Short Duration** Long Duration*
(LL-LN) 1X4.24A @ 450 W 1x70A @ 625 W
Continuous Continuous
VOLTAGE GENERATOR (6 TOTAL) LOW LEVEL SOURCES
Description Voltage Sources Number 12
6-phase AC 6 X 150 V @ 75VA Accuracy ± 0.25% of reading
(L-N)
Resolution 331 uV/bit
3-phase AC 3 X 300 V @ 150VA
(L-N)
Range
1-phase AC 1 X 600 V @ 300VA
(LL-LN) Voltage Sources 6.7 VRMS at full scale
Available Range 75V, 150V, 300V Enhanced Current 3.48 VRMS at full scale
Sources
DC
3X 424V @ 150W
(L-N) Transient Source 6.96 VRMS at full scale
All values are shown with F6005 option:
*Long Duration - 45 second duration
**Short Duration - 90 cycles
LOGIC INPUTS (VOLTAGE OR CONTACT SENSE) ANALOG INPUT MEASUREMENT AIM
Description Isolated Inputs Paired Inputs 8 external Analog or Digital
Recording
Signals
Inputs 2 (First Strike) 3 Pairs (6)
Internal Source
Voltage Sense 250 V RMS AC / 300 V dc 250 V RMS AC / 300 V dc recording 12 Sources
Open Circuit Test 12 V dc 4 V dc Ranges 250 mV, 2.5 V, 25 V, 250 V RMS
Voltage
Bandwidth DC, 0-5kHz
Short Circuit Test
20 mA dc >50 mA dc
Current Input Impedance 150KΩ
0.1 msec max pickup / Max Input Voltage 250 V RMS AC / 300 V dc
Response Time 0.1 msec max pickup /dropout
dropout
Isolation ±500 V peak channel to channel
Input Impedance 150KΩ 150KΩ
Accuracy
Isolation ±500 V peak ±500 V peak
Typical ±0.06%
LOGIC OUTPUTS
Maximum ±0.15%
FET
Description (High Speed Electronic) Relay AC AMPLITUDE ACCURACY @ 50-60 HZ @ 20° - 30° C
Number 4 4 Typical Guaranteed
Isolation Voltage ±500 V peak ±500 V peak 0.02% of reading 0.09% of reading
+ .01% of range + .04% of range
Response Time 0.1msec pick up / dropout <10 msecpick up / dropout
Playback Rate for Transient Test
(Breaking cap AC: 2000 VA
Maximum (Make/ with Vmax 250 V, Imax 8 A) 10 kHz
0.5 amps
Break Current) (Breaking cap DC: 50 W
with Vmax 300 V, Imax 8 A) CONVERTIBLE SOURCE IN CURRENT MODE
@ 20° - 30° C
Input Voltage 250 V RMS 250 V RMS
Guaranteed
VARIABLE OUTPUT BATTERY SIMULATOR
<0.5%
Range 6 - 300 V dc
TIMERS AND TRIGGERS
Resolution 0.3 V
Timers
8
Power 90 W, 1.5 A max Number
50/60 Hz Ripple <0.2% of Range Max Recording Time <24 Hours
Accuracy <±5% Accuracy ±0.0005%
of reading, ±50 µsec
METERING FUNCTIONS
Resolution 100 µsec
DC Meter Inputs
PHASE ANGLE @ 50/60 HZ
Input Range 0 - ±10 V dc / 0 - ±20 mA dc
Range Accuracy Resolution
Typical <0.003%
±360° - 0° ± 0.25° ± 0.1°
Guaranteed <0.05%
DISTORTION @ 50 /60HZ V & I SOURCES TOTAL
AC Sources
HARMONIC DISTORTION (THD)
Typical <0.02% of metering loads Typical Guaranteed
Logic Input As Counters <0.02% <0.1%
Frequency 10 kHz FREQUENCY
Pulse width >175 µsec Bandwith Range Resolution
POWER CONSUMPTION DC, 0.1 Hz - 2.0 kHZ
DC - 3 kHz at
Continuous Full 0.001 Hz
F6150e/sv at Full Power
2600W Load
Full Power
Accuracy
F6150e/sv at Idle 140W
Typical @ 20° - 30° C @ 0° - 50° C
GPS ACCURACY
With F6895 (Antenna 0.5 ppm 1.5 ppm 10 ppm
and Receiver) ± 50 nanoseconds